Search
Total
14 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2022-25622 | 1 Siemens | 23 Simatic Cfu Diq, Simatic Cfu Diq Firmware, Simatic Cfu Pa and 20 more | 2022-07-12 | 5.0 MEDIUM | 7.5 HIGH |
| A vulnerability has been identified in SIMATIC CFU DIQ (All versions), SIMATIC CFU PA (All versions), SIMATIC ET200AL IM157-1 PN (All versions), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 MF HF (All versions), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants) (All versions), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DI 16x24VDC, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DI 8x24VDC, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L (All versions >= V5.1.1), SIMATIC PN/MF Coupler (All versions), SIMATIC PN/PN Coupler (All versions >= 4.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.0.0), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions), SIMATIC TDC CP51M1 (All versions), SIMATIC TDC CPU555 (All versions), SIMATIC WinAC RTX (All versions), SIMIT Simulation Platform (All versions), SINAMICS DCM (All versions with Ethernet interface), SINAMICS G110M (All versions with Ethernet interface), SINAMICS G115D (All versions with Ethernet interface), SINAMICS G120 (incl. SIPLUS variants) (All versions with Ethernet interface), SINAMICS G130 (All versions), SINAMICS G150 (All versions), SINAMICS S110 (All versions with Ethernet interface), SINAMICS S120 (incl. SIPLUS variants) (All versions), SINAMICS S150 (All versions), SINAMICS S210 (All versions), SINAMICS V90 (All versions with Ethernet interface), SIPLUS HCS4200 CIM4210 (All versions), SIPLUS HCS4200 CIM4210C (All versions), SIPLUS HCS4300 CIM4310 (All versions), SIPLUS NET PN/PN Coupler (All versions >= 4.2). The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments. | |||||
| CVE-2019-10936 | 1 Siemens | 130 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 and 127 more | 2022-02-09 | 5.0 MEDIUM | 7.5 HIGH |
| A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, SIMATIC CFU PA, SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET200AL, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants), SIMATIC ET200S (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HS (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants), SIMATIC ET200ecoPN, 16DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 4AO U/I 4xM12, SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12, SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12, SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN: IO-Link Master, SIMATIC ET200pro, SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants), SIMATIC HMI KTP Mobile Panels, SIMATIC PN/PN Coupler (incl. SIPLUS NET variants), SIMATIC PROFINET Driver, SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX (F) 2010, SINAMICS DCM, SINAMICS DCP, SINAMICS G110M V4.7 PN Control Unit, SINAMICS G120 V4.7 PN Control Unit (incl. SIPLUS variants), SINAMICS G130 V4.7 Control Unit, SINAMICS G150 Control Unit, SINAMICS GH150 V4.7 Control Unit, SINAMICS GL150 V4.7 Control Unit, SINAMICS GM150 V4.7 Control Unit, SINAMICS S110 Control Unit, SINAMICS S120 V4.7 Control Unit (incl. SIPLUS variants), SINAMICS S150 Control Unit, SINAMICS SL150 V4.7 Control Unit, SINAMICS SM120 V4.7 Control Unit, SINUMERIK 828D, SINUMERIK 840D sl. Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial-of-service condition. The vulnerability can be triggered if a large amount of specially crafted UDP packets are sent to device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known. | |||||
| CVE-2014-2248 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 4.3 MEDIUM | N/A |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. | |||||
| CVE-2014-2251 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 8.3 HIGH | N/A |
| The random-number generator on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors. | |||||
| CVE-2014-2253 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 6.1 MEDIUM | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted Profinet packets. | |||||
| CVE-2014-2255 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 7.8 HIGH | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets. | |||||
| CVE-2014-2246 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 4.3 MEDIUM | N/A |
| Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
| CVE-2014-2259 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 7.8 HIGH | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets. | |||||
| CVE-2016-2200 | 1 Siemens | 15 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1511c-1 Pn Cpu and 12 more | 2020-02-10 | 7.8 HIGH | 7.5 HIGH |
| Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to cause a denial of service (STOP mode transition) via crafted packets on TCP port 102. | |||||
| CVE-2016-2201 | 1 Siemens | 15 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1511c-1 Pn Cpu and 12 more | 2020-02-10 | 5.0 MEDIUM | 5.3 MEDIUM |
| Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to bypass a replay protection mechanism via packets on TCP port 102. | |||||
| CVE-2014-2257 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 7.8 HIGH | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets. | |||||
| CVE-2014-2247 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2020-02-10 | 5.8 MEDIUM | N/A |
| The integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject headers via unspecified vectors. | |||||
| CVE-2014-5074 | 1 Siemens | 8 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1513-1 Pn Cpu and 5 more | 2018-05-25 | 7.1 HIGH | N/A |
| Siemens SIMATIC S7-1500 CPU devices with firmware before 1.6 allow remote attackers to cause a denial of service (device restart and STOP transition) via crafted TCP packets. | |||||
| CVE-2014-2249 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2014-03-26 | 5.8 MEDIUM | N/A |
| Cross-site request forgery (CSRF) vulnerability on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 and SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors. | |||||