CVE-2023-27857 1 Rockwellautomation 1 Thinmanager 2024-01-09 N/A 7.5 HIGH
In affected versions, a heap-based buffer over-read condition occurs when the message field indicates more data than is present in the message field in Rockwell Automation's ThinManager ThinServer.  An unauthenticated remote attacker can exploit this vulnerability to crash ThinServer.exe due to a read access violation.
CVE-2023-29031 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2023-12-20 N/A 7.1 HIGH
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.
CVE-2023-29030 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2023-12-20 N/A 7.1 HIGH
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.
CVE-2023-5909 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Keepserverex, Opc-aggregator and 5 more 2023-12-06 N/A 7.5 HIGH
KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
CVE-2023-29462 1 Rockwellautomation 1 Arena Simulation 2023-11-15 N/A 8.8 HIGH
An arbitrary code execution vulnerability contained in Rockwell Automation's Arena Simulation software was reported that could potentially allow a malicious user to commit unauthorized arbitrary code to the software by using a memory buffer overflow in the heap. potentially resulting in a complete loss of confidentiality, integrity, and availability.
CVE-2023-2914 1 Rockwellautomation 1 Thinmanager Thinserver 2023-08-23 N/A 7.5 HIGH
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, an integer overflow condition exists in the affected products. When the ThinManager processes incoming messages, a read access violation occurs and terminates the process. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and causing a denial of service condition in the software.
CVE-2023-2423 1 Rockwellautomation 2 Armor Powerflex, Armor Powerflex Firmware 2023-08-15 N/A 7.5 HIGH
A vulnerability was discovered in the Rockwell Automation Armor PowerFlex device when the product sends communications to the local event log. Threat actors could exploit this vulnerability by sending an influx of network commands, causing the product to generate an influx of event log traffic at a high rate. If exploited, the product would stop normal operations and self-reset creating a denial-of-service condition. The error code would need to be cleared prior to resuming normal operations.
CVE-2023-2263 1 Rockwellautomation 2 Kinetix 5700, Kinetix 5700 Firmware 2023-07-27 N/A 7.5 HIGH
The Rockwell Automation Kinetix 5700 DC Bus Power Supply Series A is vulnerable to CIP fuzzing.  The new ENIP connections cannot be established if impacted by this vulnerability,  which prohibits operational capabilities of the device resulting in a denial-of-service attack.
CVE-2021-27474 1 Rockwellautomation 1 Factorytalk Assetcentre 2022-07-29 5.0 MEDIUM 7.5 HIGH
Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier does not properly restrict all functions relating to IIS remoting services. This vulnerability may allow a remote, unauthenticated attacker to modify sensitive data in FactoryTalk AssetCentre.
CVE-2020-6084 1 Rockwellautomation 1 Flex I\/o 1794-aent 2022-07-29 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Logical Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability by sending an Electronic Key Segment with less bytes than required by the Key Format Table.
CVE-2020-6085 1 Rockwellautomation 1 Flex I\/o 1794-aent 2022-07-29 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Logical Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability by sending an Electronic Key Segment with less than 0x18 bytes following the Key Format field.
CVE-2020-6086 1 Rockwellautomation 2 Flex I\/o 1794-aent\/b, Flex I\/o 1794-aent\/b Firmware 2022-07-29 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Data Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability.If the Simple Segment Sub-Type is supplied, the device treats the byte following as the Data Size in words. When this value represents a size greater than what remains in the packet data, the device enters a fault state where communication with the device is lost and a physical power cycle is required.
CVE-2020-6087 1 Rockwellautomation 2 Flex I\/o 1794-aent\/b, Flex I\/o 1794-aent\/b Firmware 2022-07-29 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Data Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability If the ANSI Extended Symbol Segment Sub-Type is supplied, the device treats the byte following as the Data Size in words. When this value represents a size greater than what remains in the packet data, the device enters a fault state where communication with the device is lost and a physical power cycle is required.
CVE-2020-6083 1 Rockwellautomation 2 Allen-bradley Flex Io 1794-aent\/b, Allen-bradley Flex Io 1794-aent\/b Firmware 2022-07-29 5.0 MEDIUM 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Port Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability.
CVE-2020-5802 1 Rockwellautomation 1 Factorytalk Linx 2022-07-12 5.0 MEDIUM 7.5 HIGH
An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of FactoryTalk Linx are affected.
CVE-2020-13573 1 Rockwellautomation 1 Rslinx 2022-06-07 5.0 MEDIUM 7.5 HIGH
A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability.
CVE-2022-1118 1 Rockwellautomation 3 Connected Component Workbench, Isagraf Workbench, Safety Instrumented Systems Workstation 2022-05-26 6.8 MEDIUM 7.8 HIGH
Connected Components Workbench (v13.00.00 and prior), ISaGRAF Workbench (v6.0 though v6.6.9), and Safety Instrumented System Workstation (v1.2 and prior (for Trusted Controllers)) do not limit the objects that can be deserialized. This allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in arbitrary code execution. This vulnerability requires user interaction to be successfully exploited
CVE-2020-6111 1 Rockwellautomation 2 Micrologix 1100, Micrologix 1100 B Firmware 2022-05-12 5.0 MEDIUM 7.5 HIGH
An exploitable denial-of-service vulnerability exists in the IPv4 functionality of Allen-Bradley MicroLogix 1100 Programmable Logic Controller Systems Series B FRN 16.000, Series B FRN 15.002, Series B FRN 15.000, Series B FRN 14.000, Series B FRN 13.000, Series B FRN 12.000, Series B FRN 11.000 and Series B FRN 10.000. A specially crafted packet can cause a major error, resulting in a denial of service. An attacker can send a malicious packet to trigger this vulnerability.
CVE-2018-17924 1 Rockwellautomation 32 1756-en2f Series A, 1756-en2f Series A Firmware, 1756-en2f Series B and 29 more 2022-05-02 7.8 HIGH 8.6 HIGH
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
CVE-2020-6088 1 Rockwellautomation 2 Flex Io 1794-aent\/b, Flex Io 1794-aent\/b Firmware 2022-04-28 5.0 MEDIUM 7.5 HIGH
An exploitable denial of service vulnerability exists in the ENIP Request Path Network Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability.
CVE-2020-12028 1 Rockwellautomation 1 Factorytalk View 2022-04-25 5.5 MEDIUM 8.1 HIGH
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12029 1 Rockwellautomation 1 Factorytalk View 2022-01-04 6.8 MEDIUM 7.8 HIGH
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2019-10954 1 Rockwellautomation 10 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 7 more 2021-10-28 7.8 HIGH 7.5 HIGH
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 to 30.014 and earlier.
CVE-2020-12031 1 Rockwellautomation 1 Factorytalk View 2021-09-23 4.6 MEDIUM 7.8 HIGH
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2021-32926 1 Rockwellautomation 4 Micro800, Micro800 Firmware, Micrologix 1400 and 1 more 2021-06-15 5.0 MEDIUM 7.5 HIGH
When an authenticated password change request takes place, this vulnerability could allow the attacker to intercept the message that includes the legitimate, new password hash and replace it with an illegitimate hash. The user would no longer be able to authenticate to the controller (Micro800: All versions, MicroLogix 1400: Version 21 and later) causing a denial-of-service condition
CVE-2020-10642 1 Rockwellautomation 1 Rslinx Classic 2021-04-02 7.2 HIGH 7.8 HIGH
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic.
CVE-2021-22659 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 Firmware 2021-03-31 7.5 HIGH 8.6 HIGH
Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.
CVE-2021-22665 1 Rockwellautomation 2 Drivetools Add-on Profiles, Drivetools Sp 2021-03-25 7.2 HIGH 7.8 HIGH
Rockwell Automation DriveTools SP v5.13 and below and Drives AOP v4.12 and below both contain a vulnerability that a local attacker with limited privileges may be able to exploit resulting in privilege escalation and complete control of the system.
CVE-2020-5807 1 Rockwellautomation 1 Factorytalk Diagnostics 2020-12-30 5.0 MEDIUM 7.5 HIGH
An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected.
CVE-2020-5801 1 Rockwellautomation 1 Factorytalk Linx 2020-12-30 5.0 MEDIUM 7.5 HIGH
An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.
CVE-2020-27255 1 Rockwellautomation 1 Factorytalk Linx 2020-11-30 5.0 MEDIUM 7.5 HIGH
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR).
CVE-2020-27253 1 Rockwellautomation 1 Factorytalk Linx 2020-11-30 7.8 HIGH 7.5 HIGH
A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device.
CVE-2018-0172 2 Cisco, Rockwellautomation 8 Ios, Ios Xe, Allen-bradley Armorstratix 5700 and 5 more 2020-09-04 7.8 HIGH 8.6 HIGH
A vulnerability in the DHCP option 82 encapsulation functionality of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated, remote attacker to cause an affected device to reload, resulting in a denial of service (DoS) condition. The vulnerability exists because the affected software performs incomplete input validation of option 82 information that it receives in DHCP Version 4 (DHCPv4) packets from DHCP relay agents. An attacker could exploit this vulnerability by sending a crafted DHCPv4 packet to an affected device. A successful exploit could allow the attacker to cause a heap overflow condition on the affected device, which will cause the device to reload and result in a DoS condition. Cisco Bug IDs: CSCvg62730.
CVE-2018-0155 2 Cisco, Rockwellautomation 13 Catalyst 4500-x Series Switches \(k10\), Catalyst 4500 Supervisor Engine 6-e \(k5\), Catalyst 4500 Supervisor Engine 6l-e \(k10\) and 10 more 2020-09-04 7.8 HIGH 8.6 HIGH
A vulnerability in the Bidirectional Forwarding Detection (BFD) offload implementation of Cisco Catalyst 4500 Series Switches and Cisco Catalyst 4500-X Series Switches could allow an unauthenticated, remote attacker to cause a crash of the iosd process, causing a denial of service (DoS) condition. The vulnerability is due to insufficient error handling when the BFD header in a BFD packet is incomplete. An attacker could exploit this vulnerability by sending a crafted BFD message to or across an affected switch. A successful exploit could allow the attacker to trigger a reload of the system. This vulnerability affects Catalyst 4500 Supervisor Engine 6-E (K5), Catalyst 4500 Supervisor Engine 6L-E (K10), Catalyst 4500 Supervisor Engine 7-E (K10), Catalyst 4500 Supervisor Engine 7L-E (K10), Catalyst 4500E Supervisor Engine 8-E (K10), Catalyst 4500E Supervisor Engine 8L-E (K10), Catalyst 4500E Supervisor Engine 9-E (K10), Catalyst 4500-X Series Switches (K10), Catalyst 4900M Switch (K5), Catalyst 4948E Ethernet Switch (K5). Cisco Bug IDs: CSCvc40729.
CVE-2018-19616 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2020-08-24 6.8 MEDIUM 8.1 HIGH
An issue was discovered in Rockwell Automation Allen-Bradley PowerMonitor 1000. An unauthenticated user can add/edit/remove administrators because access control is implemented on the client side via a disabled attribute for a BUTTON element.
CVE-2019-13510 1 Rockwellautomation 1 Arena Simulation Software 2020-08-04 6.8 MEDIUM 7.8 HIGH
Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain a USE AFTER FREE CWE-416. A maliciously crafted Arena file opened by an unsuspecting user may result in the application crashing or the execution of arbitrary code.
CVE-2020-12033 1 Rockwellautomation 1 Factorytalk Services Platform 2020-07-06 5.8 MEDIUM 8.8 HIGH
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
CVE-2020-12005 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2020-06-24 7.8 HIGH 7.5 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
CVE-2020-12003 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2020-06-24 5.0 MEDIUM 7.5 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive.
CVE-2020-11999 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2020-06-24 5.5 MEDIUM 8.1 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.
CVE-2020-12034 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2020-05-22 4.8 MEDIUM 8.2 HIGH
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.
CVE-2020-6984 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2020-03-20 5.0 MEDIUM 7.5 HIGH
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable.
CVE-2020-6988 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2020-03-20 5.0 MEDIUM 7.5 HIGH
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
CVE-2013-2807 1 Rockwellautomation 1 Rslinx Enterprise 2020-02-10 7.8 HIGH 7.5 HIGH
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
CVE-2013-2806 1 Rockwellautomation 1 Rslinx Enterprise 2020-02-10 7.8 HIGH 7.5 HIGH
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
CVE-2013-2805 1 Rockwellautomation 1 Rslinx Enterprise 2020-02-10 7.8 HIGH 7.5 HIGH
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
CVE-2019-13521 1 Rockwellautomation 1 Arena Simulation 2020-02-03 6.8 MEDIUM 7.8 HIGH
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software version 16.00.00 and earlier may result in the limited exposure of information related to the targeted workstation. Rockwell Automation has released version 16.00.01 of Arena Simulation Software to address the reported vulnerabilities.
CVE-2019-13519 1 Rockwellautomation 1 Arena Simulation 2020-02-03 6.8 MEDIUM 7.8 HIGH
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software version 16.00.00 and earlier may result in the limited exposure of information related to the targeted workstation. Rockwell Automation has released version 16.00.01 of Arena Simulation Software to address the reported vulnerabilities.
CVE-2019-13527 1 Rockwellautomation 1 Arena Simulation Software 2019-10-09 6.8 MEDIUM 7.8 HIGH
In Rockwell Automation Arena Simulation Software Cat. 9502-Ax, Versions 16.00.00 and earlier, a maliciously crafted Arena file opened by an unsuspecting user may result in the use of a pointer that has not been initialized.
CVE-2018-19016 1 Rockwellautomation 2 Ethernet\/ip Web Server Module 1756-eweb, Ethernet\/ip Web Server Module 1768-eweb 2019-10-09 7.8 HIGH 7.5 HIGH
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB (includes 1756-EWEBK) Version 5.001 and earlier, and CompactLogix 1768-EWEB Version 2.005 and earlier. A remote attacker could send a crafted UDP packet to the SNMP service causing a denial-of-service condition to occur until the affected product is restarted.