Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Filtered by product Desigo Pxc5
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-24044 1 Siemens 8 Desigo Dxr2, Desigo Dxr2 Firmware, Desigo Pxc3 and 5 more 2022-06-01 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The login functionality of the application does not employ any countermeasures against Password Spraying attacks or Credential Stuffing attacks. An attacker could obtain a list of valid usernames on the device by exploiting the issue and then perform a precise Password Spraying or Credential Stuffing attack in order to obtain access to at least one account.
CVE-2021-41545 1 Siemens 8 Desigo Dxr2, Desigo Dxr2 Firmware, Desigo Pxc3 and 5 more 2022-05-19 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.