| CVE-2022-24044 | 1 Siemens | 8 Desigo Dxr2, Desigo Dxr2 Firmware, Desigo Pxc3 and 5 more | 2022-06-01 | 5.0 MEDIUM | 7.5 HIGH |
| A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The login functionality of the application does not employ any countermeasures against Password Spraying attacks or Credential Stuffing attacks. An attacker could obtain a list of valid usernames on the device by exploiting the issue and then perform a precise Password Spraying or Credential Stuffing attack in order to obtain access to at least one account. | |||||
| CVE-2021-41545 | 1 Siemens | 8 Desigo Dxr2, Desigo Dxr2 Firmware, Desigo Pxc3 and 5 more | 2022-05-19 | 5.0 MEDIUM | 7.5 HIGH |
| A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state. | |||||