Vulnerabilities (CVE)

Filtered by vendor Abb Subscribe
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2019-10995 1 Abb 16 Cp651, Cp651-web, Cp651-web Firmware and 13 more 2020-01-24 5.8 MEDIUM 8.8 HIGH
ABB CP651 HMI products revision BSP UN30 v1.76 and prior implement hidden administrative accounts that are used during the provisioning phase of the HMI interface.
CVE-2019-18247 1 Abb 4 Relion 650, Relion 650 Firmware, Relion 670 and 1 more 2019-12-11 7.8 HIGH 7.5 HIGH
An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service.
CVE-2019-7226 1 Abb 2 Pb610 Panel Builder 600, Pb610 Panel Builder 600 Firmware 2019-10-09 5.8 MEDIUM 8.8 HIGH
The ABB IDAL HTTP server CGI interface contains a URL that allows an unauthenticated attacker to bypass authentication and gain access to privileged functions. Specifically, /cgi/loginDefaultUser creates a session in an authenticated state and returns the session ID along with what may be the username and cleartext password of the user. An attacker can then supply an IDALToken value in a cookie, which will allow them to perform privileged operations such as restarting the service with /cgi/restart. A GET request to /cgi/loginDefaultUser may result in "1 #S_OK IDALToken=532c8632b86694f0232a68a0897a145c admin admin" or a similar response.
CVE-2019-7227 1 Abb 2 Pb610 Panel Builder 600, Pb610 Panel Builder 600 Firmware 2019-10-09 4.1 MEDIUM 7.3 HIGH
In the ABB IDAL FTP server, an authenticated attacker can traverse to arbitrary directories on the hard disk with "CWD ../" and then use the FTP server functionality to download and upload files. An unauthenticated attacker can take advantage of the hardcoded or default credential pair exor/exor to become an authenticated attacker.
CVE-2019-7225 1 Abb 32 Cp620, Cp620-web, Cp620-web Firmware and 29 more 2019-10-09 5.8 MEDIUM 8.8 HIGH
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.
CVE-2018-1168 1 Abb 2 Sys600, Sys600 Firmware 2019-10-09 7.2 HIGH 7.8 HIGH
This vulnerability allows local attackers to escalate privileges on vulnerable installations of ABB MicroSCADA 9.3 with FP 1-2-3. An attacker must first obtain the ability to execute low-privileged code on the target system in order to exploit this vulnerability. The specific flaw exists within the configuration of the access controls for the installed product files. The installation procedure leaves critical files open to manipulation by any authenticated user. An attacker can leverage this vulnerability to escalate privileges to SYSTEM. Was ZDI-CAN-5097.
CVE-2018-19008 1 Abb 2 Cp400pb, Cp400pb Firmware 2019-10-09 6.8 MEDIUM 7.8 HIGH
The TextEditor 2.0 in ABB CP400 Panel Builder versions 2.0.7.05 and earlier contain a vulnerability in the file parser of the Text Editor wherein the application doesn't properly prevent the insertion of specially crafted files which could allow arbitrary code execution.
CVE-2018-10616 1 Abb 1 Panel Builder 800 2019-10-09 9.3 HIGH 7.8 HIGH
ABB Panel Builder 800 all versions has an improper input validation vulnerability which may allow an attacker to insert and run arbitrary code on a computer where the affected product is used.
CVE-2017-7906 1 Abb 2 Ip Gateway, Ip Gateway Firmware 2019-10-09 6.8 MEDIUM 8.8 HIGH
In ABB IP GATEWAY 3.39 and prior, the web server does not sufficiently verify that a request was performed by the authenticated user, which may allow an attacker to launch a request impersonating that user.
CVE-2017-7920 1 Abb 4 Vsn300, Vsn300 Firmware, Vsn300 For React and 1 more 2019-10-09 5.0 MEDIUM 7.5 HIGH
An Improper Authentication issue was discovered in ABB VSN300 WiFi Logger Card versions 1.8.15 and prior, and VSN300 WiFi Logger Card for React versions 2.1.3 and prior. By accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to access internal information about status and connected devices without authenticating.
CVE-2017-16731 1 Abb 1 Ellipse 2019-10-09 2.9 LOW 8.8 HIGH
An Unprotected Transport of Credentials issue was discovered in ABB Ellipse 8.3 through Ellipse 8.9 released prior to December 2017 (including Ellipse Select). A vulnerability exists in the authentication of Ellipse to LDAP/AD using the LDAP protocol. An attacker could exploit the vulnerability by sniffing local network traffic, allowing the discovery of authentication credentials.
CVE-2018-20720 1 Abb 2 Relion 630, Relion 630 Firmware 2019-02-01 7.8 HIGH 7.5 HIGH
ABB Relion 630 devices 1.1 before 1.1.0.C0, 1.2 before 1.2.0.B3, and 1.3 before 1.3.0.A6 allow remote attackers to cause a denial of service (reboot) via a reboot command in an SPA message.
CVE-2016-2281 1 Abb 1 Panel Builder 800 2016-03-21 6.0 MEDIUM 7.2 HIGH
Untrusted search path vulnerability in ABB Panel Builder 800 5.1 allows local users to gain privileges via a Trojan horse DLL in the current working directory.