Search
Total
3 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2020-7589 | 1 Siemens | 2 Logo\! 8 Bm, Logo\! 8 Bm Firmware | 2020-12-23 | 6.4 MEDIUM | 9.1 CRITICAL |
| A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions). The vulnerability could lead to an attacker reading and modifying the device configuration and obtain project files from affected devices. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 135/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known. | |||||
| CVE-2020-25228 | 1 Siemens | 2 Logo\! 8 Bm, Logo\! 8 Bm Firmware | 2020-12-16 | 10.0 HIGH | 9.8 CRITICAL |
| A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). A service available on port 10005/tcp of the affected devices could allow complete access to all services without authorization. An attacker could gain full control over an affected device, if he has access to this service. The system manual recommends to protect access to this port. | |||||
| CVE-2020-7593 | 1 Siemens | 2 Logo\! 8 Bm, Logo\! 8 Bm Firmware | 2020-07-22 | 7.5 HIGH | 9.8 CRITICAL |
| A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (V1.81.01 - V1.81.03), LOGO! 8 BM (incl. SIPLUS variants) (V1.82.01), LOGO! 8 BM (incl. SIPLUS variants) (V1.82.02). A buffer overflow vulnerability exists in the Web Server functionality of the device. A remote unauthenticated attacker could send a specially crafted HTTP request to cause a memory corruption, potentially resulting in remote code execution. | |||||