Filtered by vendor Schneider-electric
Subscribe
Filtered by product Ecostruxure Process Expert
Subscribe
Search
Total
7 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2022-45789 | 1 Schneider-electric | 72 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 69 more | 2023-08-09 | N/A | 9.8 CRITICAL |
| A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) | |||||
| CVE-2022-45788 | 1 Schneider-electric | 108 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 105 more | 2023-08-09 | N/A | 9.8 CRITICAL |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions) | |||||
| CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2021-07-26 | 6.4 MEDIUM | 9.1 CRITICAL |
| Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | |||||
| CVE-2021-22780 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 3.6 LOW | 7.1 HIGH |
| Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file. | |||||
| CVE-2021-22781 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 2.1 LOW | 5.5 MEDIUM |
| Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file. | |||||
| CVE-2021-22782 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 2.1 LOW | 5.5 MEDIUM |
| Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file. | |||||
| CVE-2021-22778 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 3.6 LOW | 7.1 HIGH |
| Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file. | |||||