Filtered by vendor Schneider-electric
Subscribe
Search
Total
616 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2020-28212 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2022-01-31 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when a brute force attack is done over Modbus. | |||||
| CVE-2020-28213 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2022-01-31 | 6.5 MEDIUM | 8.8 HIGH |
| A CWE-494: Download of Code Without Integrity Check vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when sending specially crafted requests over Modbus. | |||||
| CVE-2020-28210 | 1 Schneider-electric | 1 Ecostruxure Building Operation | 2022-01-31 | 4.3 MEDIUM | 6.1 MEDIUM |
| A CWE-79 Improper Neutralization of Input During Web Page Generation (Cross-site Scripting) vulnerability exists in EcoStruxure Building Operation WebStation V2.0 - V3.1 that could cause an attacker to inject HTML and JavaScript code into the user's browser. | |||||
| CVE-2020-10626 | 2 Fazecast, Schneider-electric | 2 Jserialcomm, Ecostruxure It Gateway | 2022-01-31 | 6.9 MEDIUM | 7.8 HIGH |
| In Fazecast jSerialComm, Version 2.2.2 and prior, an uncontrolled search path element vulnerability could allow a malicious DLL file with the same name of any resident DLLs inside the software installation to execute arbitrary code. | |||||
| CVE-2020-7538 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2022-01-31 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause a crash of the PLC simulator present in EcoStruxureª Control Expert software when receiving a specially crafted request over Modbus. | |||||
| CVE-2020-7552 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-01-01 | 6.8 MEDIUM | 7.8 HIGH |
| A CWE-787: Out-of-bounds Write vulnerability exists in IGSS Definition (Def.exe) version 14.0.0.20247, that could cause Remote Code Execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition. | |||||
| CVE-2020-7551 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-01-01 | 6.8 MEDIUM | 7.8 HIGH |
| A CWE-787: Out-of-bounds Write vulnerability exists in IGSS Definition (Def.exe) version 14.0.0.20247, that could cause Remote Code Execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition. | |||||
| CVE-2020-7515 | 1 Schneider-electric | 1 Easergy Builder | 2021-12-10 | 2.1 LOW | 7.8 HIGH |
| A CWE-321: Use of hard-coded cryptographic key stored in cleartext vulnerability exists in Easergy Builder V1.4.7.2 and prior which could allow an attacker to decrypt a password. | |||||
| CVE-2020-7516 | 1 Schneider-electric | 1 Easergy Builder | 2021-12-10 | 2.1 LOW | 7.8 HIGH |
| A CWE-316: Cleartext Storage of Sensitive Information in Memory vulnerability exists in Easergy Builder V1.4.7.2 and prior which could allow an attacker access to login credentials. | |||||
| CVE-2021-22720 | 1 Schneider-electric | 1 C-bus Toolkit | 2021-11-30 | 6.5 MEDIUM | 7.2 HIGH |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in C-Bus Toolkit (V1.15.7 and prior) that could allow a remote code execution when restoring a project. | |||||
| CVE-2018-3693 | 6 Arm, Intel, Netapp and 3 more | 220 Cortex-a, Cortex-r, Atom C and 217 more | 2021-11-19 | 4.7 MEDIUM | 5.6 MEDIUM |
| Systems with microprocessors utilizing speculative execution and branch prediction may allow unauthorized disclosure of information to an attacker with local user access via a speculative buffer overflow and side-channel analysis. | |||||
| CVE-2020-7484 | 2 Microsoft, Schneider-electric | 4 Windows 7, Windows Nt, Windows Xp and 1 more | 2021-11-10 | 4.3 MEDIUM | 7.5 HIGH |
| **VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability with the former 'password' feature could allow a denial of service attack if the user is not following documented guidelines pertaining to dedicated TriStation connection and key-switch protection. This vulnerability was discovered and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. This feature is not present in version v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions. | |||||
| CVE-2020-7483 | 2 Microsoft, Schneider-electric | 4 Windows 7, Windows Nt, Windows Xp and 1 more | 2021-11-08 | 5.0 MEDIUM | 7.5 HIGH |
| **VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled. This vulnerability was discovered in and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. The 'password' feature is an additional optional check performed by TS1131 that it is connected to a specific controller. This data is sent as clear text and is visible on the network. This feature is not present in TriStation 1131 versions v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions. | |||||
| CVE-2019-6854 | 1 Schneider-electric | 1 Clearscada | 2021-11-03 | 4.6 MEDIUM | 7.8 HIGH |
| A CWE-287: Improper Authentication vulnerability exists in a folder within EcoStruxure Geo SCADA Expert (ClearSCADA) -with initial releases before 1 January 2019- which could cause a low privilege user to delete or modify database, setting or certificate files. Those users must have access to the file system of that operating system to exploit this vulnerability. Affected versions in current support includes ClearSCADA 2017 R3, ClearSCADA 2017 R2, and ClearSCADA 2017. | |||||
| CVE-2021-22769 | 1 Schneider-electric | 2 Easergy T300, Easergy T300 Firmware | 2021-09-20 | 4.0 MEDIUM | 4.3 MEDIUM |
| A CWE-552: Files or Directories Accessible to External Parties vulnerability exists in Easergy T300 with firmware V2.7.1 and older that could expose files or directory content when access from an attacker is not restricted or incorrectly restricted. | |||||
| CVE-2021-22704 | 1 Schneider-electric | 10 Ecostruxure Machine Expert, Harmony Gk, Harmony Gto and 7 more | 2021-09-20 | 6.4 MEDIUM | 9.1 CRITICAL |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists in Harmony/HMI Products Configured by Vijeo Designer (all versions prior to V6.2 SP11 ), Vijeo Designer Basic (all versions prior to V1.2), or EcoStruxure Machine Expert (all versions prior to V2.0) that could cause a Denial of Service or unauthorized access to system information when connecting to the Harmony HMI over FTP. | |||||
| CVE-2019-6839 | 1 Schneider-electric | 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more | 2021-09-14 | 6.5 MEDIUM | 8.8 HIGH |
| A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow a user with low privileges to upload a rogue file. | |||||
| CVE-2021-22793 | 1 Schneider-electric | 5 Accusine Pcs\+, Accusine Pcsn, Accusine Pcsn Active Harmonic Filter Firmware and 2 more | 2021-09-13 | 6.5 MEDIUM | 7.2 HIGH |
| A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exist in AccuSine PCS+ / PFV+ (Versions prior to V1.6.7) and AccuSine PCSn (Versions prior to V2.2.4) that could allow an authenticated attacker to access the device via FTP protocol. | |||||
| CVE-2021-22791 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
| CVE-2021-22790 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
| CVE-2021-22789 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
| CVE-2021-22792 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
| CVE-2021-22775 | 1 Schneider-electric | 1 Gp-pro Ex | 2021-09-10 | 4.4 MEDIUM | 7.8 HIGH |
| A CWE-427: Uncontrolled Search Path Element vulnerability exists in GP-Pro EX,V4.09.250 and prior, that could cause local code execution with elevated privileges when installing the software. | |||||
| CVE-2018-7838 | 1 Schneider-electric | 36 Bmeh582040, Bmeh582040 Firmware, Bmeh582040c and 33 more | 2021-08-18 | 7.8 HIGH | 7.5 HIGH |
| A CWE-119 Buffer Errors vulnerability exists in Modicon M580 CPU - BMEP582040, all versions before V2.90, and Modicon Ethernet Module BMENOC0301, all versions before V2.16, which could cause denial of service on the FTP service of the controller or the Ethernet BMENOC module when it receives a FTP CWD command with a data length greater than 1020 bytes. A power cycle is then needed to reactivate the FTP service. | |||||
| CVE-2018-7851 | 1 Schneider-electric | 41 140cra312xxx, 140cra312xxx Firmware, Bmeh582040 and 38 more | 2021-08-18 | 6.8 MEDIUM | 6.5 MEDIUM |
| CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could cause a denial of service to the device that would force a restart to restore availability. | |||||
| CVE-2020-7537 | 1 Schneider-electric | 38 Bmxp341000, Bmxp341000 Firmware, Bmxp342000 and 35 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
| CVE-2019-6819 | 1 Schneider-electric | 38 Bmeh582040, Bmeh582040c, Bmeh584040 and 35 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium. | |||||
| CVE-2020-7542 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, Bmxp341000 and 37 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
| CVE-2020-7543 | 1 Schneider-electric | 32 Bmxp341000, Bmxp341000 Firmware, Bmxp342000 and 29 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
| CVE-2018-3639 | 12 Arm, Canonical, Debian and 9 more | 321 Cortex-a, Ubuntu Linux, Debian Linux and 318 more | 2021-08-13 | 2.1 LOW | 5.5 MEDIUM |
| Systems with microprocessors utilizing speculative execution and speculative execution of memory reads before the addresses of all prior memory writes are known may allow unauthorized disclosure of information to an attacker with local user access via a side-channel analysis, aka Speculative Store Bypass (SSB), Variant 4. | |||||
| CVE-2021-22707 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 10.0 HIGH | 9.8 CRITICAL |
| A CWE-798: Use of Hard-coded Credentials vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to issue unauthorized commands to the charging station web server with administrative privileges. | |||||
| CVE-2021-22728 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-200: Information Exposure vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could cause disclosure of encrypted credentials when consulting the maintenance report. | |||||
| CVE-2021-22727 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-331: Insufficient Entropy vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized access to the charging station web server | |||||
| CVE-2021-22726 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 5.5 MEDIUM | 8.1 HIGH |
| A CWE-918: Server-Side Request Forgery (SSRF) vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to perform unintended actions or access to data when crafted malicious parameters are submitted to the charging station web server. | |||||
| CVE-2021-22721 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 5.0 MEDIUM | 5.3 MEDIUM |
| A CWE-200: Information Exposure vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to get limited knowledge of javascript code when crafted malicious parameters are submitted to the charging station web server. | |||||
| CVE-2021-22723 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 4.3 MEDIUM | 6.1 MEDIUM |
| A CWE-79: Improper Neutralization of Input During Web Page Generation (Cross-siteScripting) through Cross-Site Request Forgery (CSRF) vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to impersonate the user who manages the charging station or carry out actions on their behalf when crafted malicious parameters are submitted to the charging station web server. | |||||
| CVE-2021-22708 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 6.5 MEDIUM | 7.2 HIGH |
| A CWE-347: Improper Verification of Cryptographic Signature vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to craft a malicious firmware package and bypass the signature verification mechanism. | |||||
| CVE-2021-22773 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-620: Unverified Password Change vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker connected to the charging station web server to modify the password of a user. | |||||
| CVE-2021-22772 | 1 Schneider-electric | 6 T200e, T200e Firmware, T200i and 3 more | 2021-07-28 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T200 ((Modbus) SC2-04MOD-07000100 and earlier), Easergy T200 ((IEC104) SC2-04IEC-07000100 and earlier), and Easergy T200 ((DNP3) SC2-04DNP-07000102 and earlier) that could cause unauthorized operation when authentication is bypassed. | |||||
| CVE-2021-22771 | 1 Schneider-electric | 2 Easergy T300, Easergy T300 Firmware | 2021-07-28 | 6.0 MEDIUM | 7.3 HIGH |
| A CWE-1236: Improper Neutralization of Formula Elements in a CSV File vulnerability exists in Easergy T300 with firmware V2.7.1 and older that would allow arbitrary command execution. | |||||
| CVE-2021-22729 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 10.0 HIGH | 9.8 CRITICAL |
| A CWE-259: Use of Hard-coded Password vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to gain unauthorized administrative privileges when accessing to the charging station web server. | |||||
| CVE-2021-22730 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 10.0 HIGH | 9.8 CRITICAL |
| A CWE-798: Use of Hard-coded Credentials vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could an attacker to gain unauthorized administrative privileges when accessing to the charging station web server. | |||||
| CVE-2021-22774 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-28 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-759: Use of a One-Way Hash without a Salt vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could lead an attacker to get knowledge of charging station user account credentials using dictionary attacks techniques. | |||||
| CVE-2021-22706 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-27 | 4.3 MEDIUM | 6.1 MEDIUM |
| A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker to impersonate the user who manages the charging station or carry out actions on their behalf when crafted malicious parameters are submitted to the charging station web server. | |||||
| CVE-2021-22722 | 1 Schneider-electric | 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more | 2021-07-27 | 3.5 LOW | 5.4 MEDIUM |
| A CWE-79: Improper Neutralization of Input During Web Page Generation ('Stored Cross-site Scripting') vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could cause code injection when importing a CSV file or changing station parameters. | |||||
| CVE-2021-22770 | 1 Schneider-electric | 2 Easergy T300, Easergy T300 Firmware | 2021-07-27 | 4.0 MEDIUM | 6.5 MEDIUM |
| A CWE-200: Information Exposure vulnerability exists in Easergy T300 with firmware V2.7.1 and older that exposes sensitive information to an actor not explicitly authorized to have access to that information. | |||||
| CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2021-07-26 | 6.4 MEDIUM | 9.1 CRITICAL |
| Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | |||||
| CVE-2021-22780 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 3.6 LOW | 7.1 HIGH |
| Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file. | |||||
| CVE-2021-22781 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 2.1 LOW | 5.5 MEDIUM |
| Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file. | |||||
| CVE-2021-22782 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2021-07-26 | 2.1 LOW | 5.5 MEDIUM |
| Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file. | |||||