Vulnerabilities (CVE)

Filtered by vendor Rockwellautomation Subscribe
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2012-6442 1 Rockwellautomation 22 1100, 1400, 1756-enbt and 19 more 2019-09-03 7.8 HIGH N/A
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to cause a denial of service (control and communication outage) via a CIP message that specifies a reset.
CVE-2009-3739 1 Rockwellautomation 2 Ab Micrologix Controller 1100, Ab Micrologix Controller 1400 2018-10-10 10.0 HIGH N/A
Multiple unspecified vulnerabilities on the Rockwell Automation AB Micrologix 1100 and 1400 controllers allow remote attackers to obtain privileged access or cause a denial of service (halt) via unknown vectors.
CVE-2011-2530 1 Rockwellautomation 2 Eds Hardware Installation Tool, Rslinx 2018-04-10 9.3 HIGH N/A
Buffer overflow in RSEds.dll in RSHWare.exe in the EDS Hardware Installation Tool 1.0.5.1 and earlier in Rockwell Automation RSLinx Classic before 2.58 allows user-assisted remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a malformed .eds file.
CVE-2014-9204 1 Rockwellautomation 1 Rslinx 2018-04-10 6.9 MEDIUM N/A
Stack-based buffer overflow in OPCTest.exe in Rockwell Automation RSLinx Classic before 3.73.00 allows remote attackers to execute arbitrary code via a crafted CSV file.
CVE-2014-0755 1 Rockwellautomation 2 Logix 5000 Controller, Rslogix 5000 Design And Configuration Software 2017-08-29 6.9 MEDIUM N/A
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors.
CVE-2011-3489 1 Rockwellautomation 1 Rslogix 2017-08-29 5.0 MEDIUM N/A
RnaUtility.dll in RsvcHost.exe 2.30.0.23 in Rockwell RSLogix 19 and earlier allows remote attackers to cause a denial of service (crash) via a crafted rna packet with a long string to TCP port 4446 that triggers (1) "a memset zero overflow" or (2) an out-of-bounds read, related to improper handling of a 32-bit size field.
CVE-2015-6490 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2015-10-28 10.0 HIGH N/A
Stack-based buffer overflow on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices through B FRN 15.003 allows remote attackers to execute arbitrary code via unspecified vectors.
CVE-2015-6491 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2015-10-28 4.0 MEDIUM N/A
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote authenticated users to insert the content of an arbitrary file into a FRAME element via unspecified vectors.
CVE-2015-6492 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2015-10-28 7.8 HIGH N/A
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service (memory corruption and device crash) via a crafted HTTP request.
CVE-2015-6488 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2015-10-28 4.3 MEDIUM N/A
Cross-site scripting (XSS) vulnerability in the web server on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2015-6486 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2015-10-28 6.5 MEDIUM N/A
SQL injection vulnerability on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote authenticated users to execute arbitrary SQL commands via unspecified vectors.
CVE-2015-1010 1 Rockwellautomation 1 Rsview32 2015-06-02 4.9 MEDIUM N/A
Rockwell Automation RSView32 7.60.00 (aka CPR9 SR4) and earlier does not properly encrypt credentials, which allows local users to obtain sensitive information by reading a file and conducting a decryption attack.
CVE-2014-9209 1 Rockwellautomation 2 Factorytalk Services Platform, Factorytalk View Studio 2015-03-31 6.9 MEDIUM N/A
Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.
CVE-2014-5424 1 Rockwellautomation 1 Connected Components Workbench 2014-11-14 7.5 HIGH N/A
Rockwell Automation Connected Components Workbench (CCW) before 7.00.00 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via an invalid property value to an ActiveX control that was built with an outdated compiler.
CVE-2014-5410 1 Rockwellautomation 1 Ab Micrologix Controller 2014-10-06 7.1 HIGH N/A
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.
CVE-2012-4715 1 Rockwellautomation 1 Rslinx Enterprise 2013-10-02 10.0 HIGH N/A
Buffer overflow in LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a UDP packet with a certain integer length value that is (1) too large or (2) too small, leading to improper handling by Logger.dll.
CVE-2012-4690 1 Rockwellautomation 3 Ab Micrologix Controller, Plc-5 Controller, Slc 500 Controller 2013-05-21 7.1 HIGH N/A
Rockwell Automation Allen-Bradley MicroLogix controller 1100, 1200, 1400, and 1500; SLC 500 controller platform; and PLC-5 controller platform, when Static status is not enabled, allow remote attackers to cause a denial of service via messages that trigger modification of status bits.
CVE-2012-4714 1 Rockwellautomation 1 Factorytalk Services Platform 2013-04-18 7.8 HIGH N/A
Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value.
CVE-2012-4695 1 Rockwellautomation 1 Rslinx Enterprise 2013-04-18 7.1 HIGH N/A
LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage) via a zero-byte UDP packet that is not properly handled by Logger.dll.
CVE-2012-4713 1 Rockwellautomation 1 Factorytalk Services Platform 2013-04-18 7.8 HIGH N/A
Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value.
CVE-2012-6441 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 5.0 MEDIUM N/A
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to obtain sensitive information via a crafted CIP packet.
CVE-2012-6440 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 9.3 HIGH N/A
The web-server password-authentication functionality in Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allows man-in-the-middle attackers to conduct replay attacks via HTTP traffic.
CVE-2012-6439 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 8.5 HIGH N/A
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to cause a denial of service (control and communication outage) via a CIP message that modifies the (1) configuration or (2) network parameters.
CVE-2012-6438 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 7.8 HIGH N/A
Buffer overflow in Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allows remote attackers to cause a denial of service (NIC crash and communication outage) via a malformed CIP packet.
CVE-2012-6437 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 10.0 HIGH N/A
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 do not properly perform authentication for Ethernet firmware updates, which allows remote attackers to execute arbitrary code via a Trojan horse update image.
CVE-2012-6436 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 7.8 HIGH N/A
Buffer overflow in Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allows remote attackers to cause a denial of service (CPU crash and communication outage) via a malformed CIP packet.
CVE-2012-6435 1 Rockwellautomation 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more 2013-01-25 7.8 HIGH N/A
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to cause a denial of service (control and communication outage) via a CIP message that specifies a logic-execution stop and fault.
CVE-2012-0221 1 Rockwellautomation 2 Factorytalk, Rslogix 5000 2012-04-03 5.0 MEDIUM N/A
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet.
CVE-2012-0222 1 Rockwellautomation 2 Factorytalk, Rslogix 5000 2012-04-03 5.0 MEDIUM N/A
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet.
CVE-2011-2957 1 Rockwellautomation 1 Factorytalk Diagnostics Viewer 2011-08-12 6.9 MEDIUM N/A
Unspecified vulnerability in Rockwell Automation FactoryTalk Diagnostics Viewer before V2.30.00 (CPR9 SR3) allows local users to execute arbitrary code via a crafted FactoryTalk Diagnostics Viewer (.ftd) configuration file, which triggers memory corruption.
CVE-2009-0474 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2011-03-08 5.0 MEDIUM N/A
The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603.
CVE-2009-0473 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2011-03-08 6.8 MEDIUM N/A
Open redirect vulnerability in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors.
CVE-2009-0472 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2011-03-08 4.3 MEDIUM N/A
Multiple cross-site scripting (XSS) vulnerabilities in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allow remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2010-2965 2 Rockwellautomation, Windriver 3 1756-enbt Series A, 1756-enbt Series A Firmware, Vxworks 2010-08-05 10.0 HIGH N/A
The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756-ENBT series A with firmware 3.2.6 and 3.6.1 and other products, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185, a related issue to CVE-2005-3804.