Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Filtered by product Unity Pro
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2019-6855 1 Schneider-electric 44 Ecostruxure Control Expert, Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware and 41 more 2022-01-31 7.5 HIGH 7.3 HIGH
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
CVE-2020-7560 1 Schneider-electric 2 Ecostruxure Control Expert, Unity Pro 2022-01-31 6.8 MEDIUM 8.6 HIGH
A CWE-123: Write-what-where Condition vulnerability exists in EcoStruxure™ Control Expert (all versions) and Unity Pro (former name of EcoStruxure™ Control Expert) (all versions), that could cause a crash of the software or unexpected code execution when opening a malicious file in EcoStruxure™ Control Expert software.
CVE-2016-8354 1 Schneider-electric 1 Unity Pro 2017-03-15 5.1 MEDIUM 7.0 HIGH
An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.