Search
Total
4 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2022-33318 | 2 Iconics, Mitsubishielectric | 2 Genesis64, Mc Works64 | 2022-07-27 | N/A | 9.8 CRITICAL |
| Deserialization of Untrusted Data vulnerability in ICONICS GENESIS64 versions 10.97.1 and prior and Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior allows a remote unauthenticated attacker to execute an arbitrary malicious code by sending specially crafted packets to the GENESIS64 server. | |||||
| CVE-2022-33319 | 2 Iconics, Mitsubishielectric | 2 Genesis64, Mc Works64 | 2022-07-27 | N/A | 9.1 CRITICAL |
| Out-of-bounds Read vulnerability in ICONICS GENESIS64 versions 10.97.1 and prior and Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior allows a remote unauthenticated attacker to disclose information on memory or cause a Denial of Service (DoS) condition by sending specially crafted packets to the GENESIS64 server. | |||||
| CVE-2022-23128 | 2 Iconics, Mitsubishielectric | 5 Analytix, Genesis64, Hyper Historian and 2 more | 2022-01-27 | 7.5 HIGH | 9.8 CRITICAL |
| Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products. | |||||
| CVE-2020-12013 | 2 Iconics, Mitsubishielectric | 11 Bizviz, Energy Analytix, Facility Analytix and 8 more | 2021-11-04 | 6.4 MEDIUM | 9.1 CRITICAL |
| A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior. | |||||