A vulnerability has been identified in Opcenter Quality (All versions), SIMATIC PCS neo (All versions < V4.1), SINUMERIK Integrate RunMyHMI /Automotive (All versions), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an improper input validation vulnerability that could allow an attacker to bring the service into a Denial-of-Service state by sending a specifically crafted message to 4004/tcp. The corresponding service is auto-restarted after the crash is detected by a watchdog.
References
| Link | Resource |
|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-999588.pdf | Patch Vendor Advisory |
Configurations
Configuration 1 (hide)
|
Information
Published : 2023-12-12 12:15
Updated : 2024-01-09 10:15
NVD link : CVE-2023-46285
Mitre link : CVE-2023-46285
JSON object : View
Products Affected
siemens
- opcenter_quality
- simatic_pcs_neo
- totally_integrated_automation_portal
- sinumerik_integrate_runmyhmi_\/automotive
CWE