CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
CVSS

No CVSS.

Configurations

No configuration.

Information

Published : 2022-07-26 22:15

Updated : 2022-07-27 07:24


NVD link : CVE-2022-31204

Mitre link : CVE-2022-31204


JSON object : View

Products Affected

No product.

CWE

No CWE.